DLRO10HD Heavy Duty 10A Low Resistance Ohmmeter
Heavy duty low resistance ohmmeter combining rugged construction with accuracy and ease of use. It features an internal rechargeable battery and can also operate from a mains supply, even if the battery is completely flat
2 high power ( up to 25W) ranges ideal for inductive applications, and where heating a potential weakness is desirable
7 low power output ranges limited to 0.25W to avoid heating the test piece and to extend battery life.
Rechargeable battery or line power supply, continuous operation, even with dead battery
10 A for 60 seconds, less time waiting to cool, great for charging inductance
High input protection to 600 V, inadvertent connection to line or UPS voltage will not blow a fuse
Heavy duty case: IP 65 lid closed, IP54 operational (battery operation only)
Large backlit LCD is clear and easy to read in all lighting conditions.
Rotary switch selects one of five test modes, including auto start on connection, giving ease of use
DH5 straight duplex handspike set with 2.5m long leads. See stock no.
666-7371
Support accessories:
Test Current
Resistance Range
Resolution
Accuracy *
Full scale voltage
Max. power output
0.1 mA
0 → 2500.0 Ω
100 mΩ
±0.2% ±200 mΩ
25 mV
2.5 μW
0.1 mA
0 → 250.00 Ω
10 mΩ
±0.2% ±20 mΩ
25 mV
2.5 μW
1 mA
0 → 25.000 Ω
1 mΩ
±0.2% ±2 mΩ
25 mV
25 μW
10 mA
0 → 2500.0 mΩ
100 μΩ
±0.2% ±200 μΩ
25mV
250 μW
100 mA
0 → 250.00 mΩ
10 μΩ
±0.2% ±20 μΩ
25 mV
2.5 mW
1 A
0 → 25.000 mΩ
1 μΩ
±0.2% ±2 μΩ
25 mV
25 mW
10 A
0 → 2500.0 μΩ
0.1 μΩ
±0.2% ±0.2 μΩ
25 mV
0.25 W
1 A
0 → 2500.0 mΩ
100 μΩ
±0.2% ±200 μΩ
2.5 V
2.5 W
10 A
0 → 250.00 mΩ
10 μΩ
±0.2% ±20 μΩ
2.5 V
25 W
* The accuracy stated assumes forward and reverse measurements.
Inductive mode or unidirectional mode will introduce an undefined error if an external EMF...